Technical Bulletin – Lead Crystal Charging and Comissioning

Lead Crystal Charging and commissioning requirements. Initial charging current to be 0.3C ( IE 30 amps for each 100 A/H)a.This requirement is important and must be adhered too at all times. Bulk charging voltage is 2.45volt per cell @ 25°C (14.7 v for a 12volt block)a.Charging below this rate will result in partial charging [...]